Comparison Analysis of Partial Discharge Detection Methods in Cast Resin Dry Type Transformers

몰드변압기에서 부분방전 검출방법의 비교분석

  • Published : 2008.10.17

Abstract

Various sensors such as capacitive probe, high frequency current transformer (HFCT), and acoustic emission (AE) probe were applied to a cast resin dry type transformer for partial discharge detection. We designed and fabricated a wideband low-noise amplifier having a gain of 40[dB]. From the experiment which was carried out in the same transformer, the sensitivities were 7.16[mV/pC] for capacitive probe, 3.8[mV/pC] for HFCT, and 17.9[mV/pC] for AE probe.

Keywords