Co-combustion of RPF in the Coal Power plant

석탄보일러에서 각종 RDF혼소시 다이옥신 농도 조사

  • 최연석 (한국기계연구원 환경기계연구본부) ;
  • 최항석 (한국기계연구원 환경기계연구본부) ;
  • 김석준 (한국기계연구원 환경기계연구본부) ;
  • 윤균덕 (한국산업기술시험원 환경기술센터)
  • Published : 2008.05.22

Abstract

The co-combustion of coal and three kinds of RDFs(Refuse Plastic Fuel) mixture has been experimented in a commercially operating CFB coal boiler respectively and the pollutant emissions such as SOx, NOx, TSP and dioxine were measured at the stack. The mixing ratio with coal was 7.5% RPF, 7.5% RDF and 10% SDF respectively. During co-combustion, dioxine emission level was very low and SOx, NOx and TSP were decreased comparing the single coal combustion. Emitting dioxine concentration was proportioned to the chlorine content of RDF. These RPF, SDF and RDF could be determined to be a good alternative fuel of general coal.

Keywords