환기상태 분석에 따른 급 배기구 위치 평가

Evaluation of the location of the Outlets according to the Analysis of Ventilation conditions

  • 문용준 (서울시립대학교 산업기술연구소) ;
  • 김혁순 (서울시립대학교 기계정보공학과 대학원) ;
  • 곽명근 (서울시립대학교 기계정보공학과 대학원) ;
  • 오명도 (서울시립대학교 기계정보공학과)
  • Moon, Yong-Jun (Institute of Industrial Technology, University of Seoul) ;
  • Kim, Hyouk-Soon (Graduate school of Mechanical and Information Engineering, University of Seoul) ;
  • Kwak, Myong-Keun (Graduate school of Mechanical and Information Engineering, University of Seoul) ;
  • Oh, Myung-Do (Department of Mechanical and Information Engineering, University of Seoul)
  • 발행 : 2008.06.25

초록

The purpose of this study is to evaluate the location of the outlets in the mechanical ventilation system installed in apartment. We performed the numerical analysis to estimate the ventilation effectiveness and the indoor $CO_2$ concentration considering the occupants and the condition with inlet and outlet in each room. From the numerical results, modified location of the outlets is about 10% high than designed one with respect to the ventilation effectiveness when the occupants are not considered. But designed location of inlet and outlet in living room and kitchen is better than modified one with respect to the reduction of $CO_2$ concentration in the living room and kitchen with occupants. In case of our model, Air change per hour (0.7) is not enough to sustain the acceptable criteria of $CO_2$ concentration (1000ppm) in the room with the occupants