Thermal Response Property of Grout Materials from In-situ Test and Temperature Variation of Ground Heat Exchanger

그라우트 재료별 열응답 특성 및 열교환기 운전온도 변화

  • 김갑득 (제이비에너텍 기술연구소) ;
  • 이성주 (제이비에너텍 기술연구소) ;
  • 윤여상 (제이비에너텍 기술연구소)
  • Published : 2008.06.25

Abstract

The objective of this report is to determine the difference of thermal response that grouted two different materials, and compare the simulation result of the length of total ground heat exchanger length that using the ground thermal conductivity. And also to know heat exchange variation of ground heat exchanger temperature that measured with various test depth. The result shows that the test hole grouted with water permeable material got better thermal response than grouted with water impermeable material. However, with consideration of ingnore for the initial 12 hour data, the test hole grouted with impermeable material has larger thermal conductivity than the other. By former thermal conductivity, simulated data by engineering program shows only 3.4% difference or less. This result shows that ground thermal conductivity is not the main variables for the design program of ground heat exchanger. At the cooling or heating mode, base on the depth of -150m, the ground heat exchanger has best temperature at $-90{\sim}-60m$ and than getting worse because of entering water heat exchanged with leaving water in the same hole.

Keywords