A Study on the Abnormal Heating of Circuit Breaker in Panel Board by Poor Connection

분전반 내 차단기의 접속불량에 의한 이상발열에 관한 연구

  • Published : 2008.04.17

Abstract

In this paper, abnormal heating of circuit breaker in panel board by poor connection was studied. Firstly, calculation method of contact resistance shown in IEC 60943 was examined. Secondly, concerning abnormal heating of circuit breaker in panel board, field measurements were performed. Field measurements showed that locally abnormal heating by poor connection could be detected, therefore, in that case, immediate action was needed. Finally, experiments regarding abnormal heating between terminal of circuit breaker and electric wire were conducted. The results showed that abnormal heating above $180^{\circ}C$ was measured. Also, in the results of analysis of electrical waveforms according to load current, voltage drop occurred around poor connection, and the oxide was generated according to mechanical vibration. In order to prevent electrical disaster caused by poor connection, adequate torque should be applied to electrical connection, and periodic check-ups are needed.

Keywords