The Study on the Dry and Wet Flashover Voltages of the Artificially Salt Contaminated Distribution Facilities

인공오손에 따른 배전기자재의 건조 및 습윤 섬락에 관한 연구

  • Published : 2008.06.19

Abstract

The dry and wet flashover characteristics on the contaminated distribution facilities was investigated. The test were carried out on the suspension insulator, line post insulator, lightning arrester, cut off switch, etc. In the dry state, the flashover voltages of facilities contaminated with B, C, D classes are similar to the non-contaminated ones. However, in the wet state, the flashover voltages of facilities contaminated with B, C, D classes are decreased. The flashover voltages of some few facilities show under the standard value. This results indicate that the high humidity may cause the flashover on distribution facilities.

Keywords