Lateral Resisting Capacity for CFT Column to RC Flat Plate Slab Exterior Connections

CFT 기둥-RC 무량판 슬래브 외부접합부의 횡저항 성능

  • Published : 2008.11.07

Abstract

A combination of CFT column and RC flat plate without formworks is very effectively rapid constructions. This paper verified the lateral resisting capacity of CFT column-RC flat plate exterior connection in comparison with general RC column-flat plate connection and detected moment capacity and ductility capacity of connection according to moment-displacement ratio. We made and tested specimens which have different variables respectively and as a result derive a following conclusion. In CFT-E2 specimen a critical section was extended and maximum moment increased 20% respectively in comparison to general RC column specimen. In BME and CFT-E1 specimens generally shear governed behaviors and CFT-E2 specimen complemented with seismic band, flexure behavior region of slab was extended and also ductility ratio and energy absorptance increased.

콘크리트충전 강관기둥(Concrete Filled steel Tube Column)과 RC 무량판 슬래브의 조합은 거푸집을 사용하지 않는다는 것만으로도 초고층 건물의 공기단축에 상당한 영향을 미칠 수 있다. 뿐만 아니라 기둥의 내력 증진으로 인한 기둥 크기의 축소, 그로 인한 공간 활용도의 증가, 층간 소음문제 해결 등 많은 장점이 잠재되어 있다. 하지만 접합부의 성능을 정확히 밝혀내는 것이 우선 이루어져야 하며, 본 논문에서는 기존에 수행된 CFT 기둥-RC 무량판 슬래브의 내부접합부에 대한 중력 실험과 횡하중 실험을 바탕으로 외부접합부에 대한 실물대 실험을 수행하였다. 외부접합부 실험 결과, 내부접합부 실험체에 비하여 동일한 조건에서 설계된 외부접합부 실험체는 최대 모멘트강도가 $50%{\sim}65%$ 감소하였고, 내진밴드가 추가된 CFT-E2 실험체는 BME 실험체에 비하여 20%의 최대모멘트 증진과 탁월한 연성능력, 에너지 흡수능력을 보유한 것으로 나타났다. 또한 CFT-E2는 내진밴드의 사용으로 슬래브의 휨거동 영역이 확장되었으며 모든 실험체가 설계기준에서 요구하는 0.4V$_c$중력하중 하에서 1.5% 횡변 위비를 만족하였다.