초록
In this paper, we dealt with a partial discharge (PD) measurement method that has been accepted as an effective and non-destructive technique to estimate insulation performance of low-voltage induction motors. The PD measurement system consists of a coupling network, a low noise amplifier, and associated electronics. A shielded box was used to reduce environmental noise. Frequency characteristic of the coupling network was estimated by a sinusoidal signal input, and the low cut-off frequency of the coupling network was 1 MHz (-3 dB). Also, we carried out a calibration test for the PD measurement system. Sensitivity of the system was of 84 m