Characteristics of Dissipation Factor in High Voltage Motor Stator Windings

고압전동기 고정자 권선의 유전정접 특성

  • Published : 2008.10.31

Abstract

Diagnostic tests were performed in three high voltage motors. These tests included insulation resistance, polarization index, ac current, dissipation factor($tan{\delta}$) and partial discharge magnitude. The rewind of motor stator insulation at rated voltage is assessed by the results of these tests. After completing the diagnostic tests, the stator windings of motors were subjected to gradually increasing ac voltage, until the insulation punctured. NO.1 and No.2 motors failed near rated voltage of 14.0 kV, respectively. These motors are lower that expected for good quality coils in 6.6 kV class motors. The breakdown voltage of No.3 motor was 15.0 kV.