Evaluation of IEAR(Interrupted Energy Assessment Rates) using Macro Approach in Korea
거시적방법에 의한 우리나라의 종합공급지장비단가 추정
- Park, Jeong-Je (Gyeongsang National University) ;
- Wu, Liang (Gyeongsang National University) ;
- Choi, Jae-Seok (Gyeongsang National University) ;
- Jung, Yong-Bum (KEPRI) ;
- Yoon, Yong-Bum (KEPRI)
- Published : 2008.11.07
Abstract
This paper introduces the characteristics of relationship between probabilistic reliability (LOLE; Loss of Load Expectation) and deterministic reliability (SRR; supply reserve rate) for 2008 year in Korea power system. Korea power system has been using the LOLE criterion to determine the adequacy of installed capacity (ICAP) requirement. The criterion is that load shall not exceed the avaliable capacity, on the average, more than five day in ten years. The probabilistic reliability evaluation and production cost simulation program which is called PPHFHT was used in order to obtain the relationship in this paper.
Keywords