Proceedings of the KIEE Conference (대한전기학회:학술대회논문집)
- 2008.04c
- /
- Pages.245-246
- /
- 2008
Analysis of arc driving force for 3 petal and 4petal of spiral type vacuum interrupter by FEM analysis
FEM 해석을 통한 Spiral type 진공인터럽터의 전극형상에 따른 아크구동력 비교
- Kim, Byoung-Chul (Chungbuk University) ;
- Yoon, Jae-Hun (Chungbuk University) ;
- Hoe, Jun (Chungbuk University) ;
- Kang, Seong-Hwa (Chungcheong college) ;
- Lim, Kee-Joe (Chungbuk University)
- Published : 2008.04.25
Abstract
In this paper we calculated and compared the arc driving force of two spiral-tyre vacuum interrupter electrode models which have 3petals and 4petals respectively by means of commercial finite element method software Maxwell 3D. As a result we can find that the more petals the electrode has, the stronger arc driving force was generated. This simulation method can contribute to optimization of spiral-type electrode designs in a view of arc driving force.
Keywords