A Study on Improving the Efficiency of Ground Heat Exchanger

지중열교환기 성능 향상에 관한 연구

  • 김욱중 (한국기계연구원 에너지기계연구본부) ;
  • 이공훈 (한국기계연구원 에너지기계연구본부) ;
  • 김민수 ((주) 탑솔)
  • Published : 2008.11.05

Abstract

A simple transient simulation of ground source heat pump system was carried out to investigate the effects of ground thermal conductivity on its performance. The TRNSYS code with a simple water to water heat pump model was used to compare the COP variation of the system. A new ground heat exchanger called by semi-closed loop was proposed and constructed in the real site. The effective thermal conductivity was measured using the test equipment developed by according to the line source model. The simulation results showed that highly efficient thermal conductivity of the grout material could increase the performance of the heat pump system very well. And the new ground heat exchanger showed the increased effective thermal conductivity as the penetration water flow rate(PWFR) was increased. Therefore, the performance improvement of the heat pump system using the proposed ground heat exchanger can be expected.

Keywords