Performance Evaluation of plate heat exchanger with chevron angle variation

쉐브론 각도변화에 따른 판형 용액열교환기의 성능평가

  • 권오경 (한국생산기술연구원 열유체시스템팀) ;
  • 차동안 (한국생산기술연구원 열유체시스템팀) ;
  • 윤재호 (한국생산기술연구원 열유체시스템팀) ;
  • 김효상 (삼중테크 (주))
  • Published : 2008.11.05

Abstract

The objectives of this paper are to measure the heat transfer and pressure drop of the plate heat exchangers for absorption system applications. Three types of plate heat exchangers with different chevron angles are tested in the present experiment. Heat transfer and pressure drop performance of plate heat exchangers are measured in various operating conditions, and compared each other. The results show that the heat transfer rate of high theta ($120^{\circ}$) and mixed theta plate heat exchanger increases about 118% and 98% at the solution flow rate 350 kg/h compared to that of low theta ($60^{\circ}$), respectively. The effectiveness of high theta was evaluated about $0.70{\sim}0.83$ in this experimental range.

Keywords