Allowable sound pressure levels of ceiling mounted air-conditioning sounds

천장형 에어컨 소음의 허용 음압레벨 도출

  • 유진 (한양대학교 건축환경공학과) ;
  • 정충일 (한양대학교 건축환경공학과) ;
  • 전진용 (한양대학교 건축대학)
  • Published : 2008.04.17

Abstract

Noises from ceiling mounted air-conditioning units were recorded in various actual situations such as offices, classrooms and libraries. Eight specimens of air-conditioners from major domestic and foreign manufacturers' were investigated in this study. A head and torso simulator was located 1.5 m beneath the air-conditioner panel for the measurements and sound pressure levels of the recording sounds were varied from 28 to 55 dBA with 3 dB steps for subjective evaluations. A total of 88 stimuli was randomly presented to subjects using a headphone system in semi-anechoic chamber. Two-categorized (noisiness and amenity) nine-point scale was used as evaluation method. The third scale ('point 3') among the nine-point scale was set as the threshold of allowable level of the air-conditioning sounds in consideration of the real situations. The results indicate that the allowable sound pressure level is around 34 dBA for both noisiness and amenity categories.

Keywords