Discharge Phenomena of Low Pressure Vacuum under AC Applied Voltage

교류전압하에서 저압 진공관의 방전현상

  • 전진 (동신대학교 전기공학과) ;
  • 최용성 (동신대학교 전기공학과) ;
  • 이경섭 (동신대학교 전기공학과)
  • Published : 2008.07.16

Abstract

We experimentally investigated discharge phenomena inside vacuum interrupter at 1 to 20 Torr to simulate the vacuum leakage. We used glass type of vacuum interrupter where the internal pressure and the type of gasses can be varied according to requirement. The experiment is conducted under ac applied voltage and the experimental circuit is constructed to simulate the actual circuit used in cubical type insulated switchgear. We used two types of gases such as air and SF6. The use of glass type vacuum interrupter allowed us to measure discharges occurring in vacuum interrupter optically. We measured and discussed the discharge occurring in both gases with a current transformer and ICCD camera. We also revealed that electromagnetic wave spectra emitted by the discharge have same frequency range for both gasses.

Keywords