대한전기학회:학술대회논문집 (Proceedings of the KIEE Conference)
- 대한전기학회 2008년도 제39회 하계학술대회
- /
- Pages.808-809
- /
- 2008
22.9kV/50MVA급 고온초전도 전력케이블의 DC Ic 측정 및 교류손실에 관한 연구
The study on the DC Ic measurement and AC loss in the 22.9kV, 50MVA HTS power cable
- Choi, Suk-Jin (Uiduk Univ) ;
- Lee, Sang-Jin (Uiduk Univ) ;
- Sim, Ki-Deok (Electrotechnology Research Institute) ;
- Cho, Jeon-Wook (Electrotechnology Research Institute)
- 발행 : 2008.07.16
초록
22.9kV 50MVA HTS power cable has been developed and tested by Korea Electrotechnology Research Institute and LS Cable Company and it was supported by a grant from Center for Applied Superconductivity Technology of the 21st Century Frontier R&D Program. In this paper, DC Ic of 100m HTS cable which is installed at Kochang testing station was measured and analyzed. A measurement technique of DC Ic used by resistance and inductance removal method is established. The HTS power cable is composed of 2 layers for transmission and 1 layer for shield. For the analysis of AC losses in an HTS power cable, 2-dimensional numerical calculation was carried out to define the magnetic field distribution. We calculated the magnetization losses in the HTS core of that cable from these fields. These calculated results are in accordance with those of experiment.
키워드