초록
In this paper, we developed DSP based control system to automatically open and close passive filter, which is used to reduce harmonics, according to operating condition of loads. Passive filter control system automatically open and close each branch of filter according to working conditions of loads by sending signals to open and close installation of passive filter after measuring and monitoring voltage, current, harmonics, reactive power, power factor and so on. We verified it's performance by connecting control system with passive filter in the power line using the 100[HP] d.c. motor drive, opening and closing passive filter according to operation condition of motor, and measuring harmonics and reactive power, etc.