고압계통 지락고장시 인체안전에 미치는 영향

Effects of Ground Faults on the Safety of Persons in High Voltage Distribution Systems

  • 강성만 (대한전기협회 기술기준처) ;
  • 김한수 (대한전기협회 기술기준처) ;
  • 이종철 (대한전기협회 기술기준처) ;
  • 이주철 (대한전기협회 기술기준처)
  • 발행 : 2007.11.02

초록

This paper presents experimental results on the safety of persons due to a ground fault in 22.9 kV-Y distribution system In order to evaluate the touch voltages due to internal ground faults in a step down transformer based on the newly prescribed KS C IEC 60364 standard series, the verification tests in a 22.9 kV multi-grounded neutral system were carried out From the experimental results, it was found that there will be significant potential rise jeopardizing LV equipment insulation in case of separate grounding between HV and LV system and the effective measures against hazardous touch voltages due to a IN side ground fault in the common grounding system between HV and LV system are proposed. As a consequence, it was found that the equipotential bonding is an important prerequisite for the effectiveness of the protective measures for the safety of persons in the common ground system between 22.9 kV-Y and low-voltage grounding system.