Effect of the Tube Geometry and Arrangement on the Performance of a High Temperarture Generator

고온재생기 성능 변화에 미치는 전열관 형상 및 배열의 영향

  • Lee, In-Song (Graduate School, School of Mechanical Engineering, Sungkyunkwan University) ;
  • Cho, Keum-Nam (DSchool of Mechanical Engineering, Sungkyunkwan University)
  • Published : 2007.11.30

Abstract

The present study numerically investigated the tube geometry and arrangement on the performance of a high temperature generator (HTG) of the double effect LiBr-water absorption system. FLUENT, as a commercial code, was used to estimate the thermal performance of the HTG. Key parameters were the spacing raito of circular and flattened tubes, the pitch ratio of the rib on the flattened tube, and total heat transfer area of the HTG. Temperature and velocity profiles around the tubes of the HTG were calculated to estimate the thermal performance of the HTG. When the spacing ratio of circular and flattened tube is 1.11 and 0.73, the exhaust gas temperature is $185^{\circ}C$ without rib. The exhaust gas temperature when applied the rib in flattened tubes was lower by $24^{\circ}C$ than that without the rib. Rib can reduce the HTG volume by 7%.

Keywords