Effect of air velocity on frost formation of slit fin-and-tube heat exchanger under frosting condition

착상 시 공기 유속이 슬릿 핀-관 열교환기 서리층 생성에 미치는 영향에 관한 연구

  • Shin, Sung-Hong (Graduate school, Sungkyunkwan University) ;
  • Cho, Keum-Nam (School of Mechanical Engineering, Sungkyunkwan University) ;
  • Hayase, Gaku (System Appliances Division, Samsung Electronics Co., Ltd)
  • Published : 2007.11.30

Abstract

The present study investigated the effect of air velocity on frost formation of slit fin-and-tube heat exchanger under frosting condition. The slit fin-and-tube heat exchanger with outer tube diameter 7.0mm and 1 row was used. Air side pressure drop, photographs of frost distribution, frost accumulation and frost thickness were presented with respect to the frosting time. In the early stage of experiment, the case with air velocity of 1.5m/s showed 403% higher for the air pressure drop than the case with the air velocity of 0.5m/s. As the frost was accumulated, the effect of air velocity on air pressure drop was decreased. In the end stage of test, air pressure drops of two cases were very close and air pressure drop for the air velocity of 0.5m/s was higher than that of 2.0m/s. It was also shown in the photographs of frost distribution, frost accumulation and frost thickness. From frost thickness, fanning friction factor was presented.