154kV급 중간접속부내의 부분방전 진단을 위한 HFCT 적용 기준신호 측정
Measurement of Basis Signal with HFCT for Diagnosing Partial Discharge in Middle Joint Box of 154kV Grade
- Ahn, Jong-Hyun (Dongshin Univ.) ;
- Yun, Ju-Ho (Dongshin Univ.) ;
- Choi, Yong-Sung (Dongshin Univ.) ;
- Park, Dae-Hee (Wonkwang University) ;
- Lee, Kyung-Sup (Dongshin Univ.)
- 발행 : 2007.04.20
초록
To detect partial discharge of 154kV joint box, we have made experiment by using the HFCT sensor. Generally the signals which are detected in partial discharge test of underground power transmission cable are accompanied with both noises of high voltage and noises of surrounding power cable. The most noise in near to end part of joint box is corona, beside other noises flowed from surrounding area. Partial discharge test is difficulty due to these noises. First, we test reliability on both injection of calibration signal in NJB and removal of low frequency. After that, we had analyzed frequencies by measuring signals in IJB with 300[m] distance from NJB. Also we had measured S/N ratio by using the indirected injection method of calibration signal in IJB. In this experiment, two measurement methods were difference of detection acquisition, but these had the equal frequency properties.