중성점을 이용한 변압기형 초전도 한류기의 전류제한 특성 분석

Current Limiting Characteristics of transformer type SFCL using neutral line

  • Cho, Yong-Sun (Electrical Engineering Department of ChoSun University) ;
  • Choi, Hyo-Sang (Electrical Engineering Department of ChoSun University) ;
  • Park, Hyoung-Min (Electrical Engineering Department of ChoSun University) ;
  • Lee, Ju-Hyoung (Electrical Engineering Department of ChoSun University) ;
  • Jung, Byung-Ik (Electrical Engineering Department of ChoSun University)
  • 발행 : 2007.07.18

초록

We investigated the characteristics of transformer type SFCL with neutral line. The transformer type SFCL having neutral line has achieved the simultaneous quench because the secondary winding has acted as parallel reactor. The fault current of SFCL was limited according to ratio of turn number between primary and secondary windings. Therefore, the power burden of superconducting element can be reduced by reduction of ratio of turn number between primary and secondary windings. As a result, we could expect reduction of it's volume in the transformer type SFCL.

키워드