풍력 유도발전기의 여자 축전지에 따른 고주파 증폭에 관한 기술 동향

Technical Trend on Excitation Capacitors on Harmonic Amplification of Wind Induction Generator

  • 발행 : 2007.07.18

초록

This paper introduce the electrical quantities of a three-phase-connected wind induction generator (WIG) under sudden connection of static loads. An intelligent power-system recorder/monitor is employed to measure threephase voltages and currents of the studied system at WIG's terminals and load's terminals for 5 minutes. A laboratory 300 W wound-rotor induction machine driven by a blushless DC motor is utilized as the studied WIG. Since the generated harmonic currents are randomly varied, total harmonic distortion (THD) of current using cumulative probability density function is employed to determine the penetration of harmonic distortion. The results show that the harmonic currents generated by the studied WIG may be severely amplified to a high level by the connected self-excited capacitance at the stator's terminals.

키워드