Electrical Breakdown Characteristics of Epoxy and dry-air Composite Insulation

에폭시와 dry-air 혼합절연물의 절연파괴특성

  • Published : 2007.07.18

Abstract

SF6 gas used widely as insulating component is rising as the environment problem. Electrical breakdown characteristics of epoxy and dry-air composite insulation was investigated on thickness of epoxy and pressure of dry-air under non-uniform field. The gap of needle to plane was from 2mm to 5mm. The pressure of dry-air was varied within the range of $0.1{\sim}0.6$ MPa. The thickness of a needle was 1mm and the curvature radius of a needle end was 100um. The diameter of a plane made of the stainless steel was 50mm. As a result of the experiment, breakdown voltage was increased about 3 times when epoxy was used. The impact that the thickness of epoxy influences on breakdown voltage was poor. It needs suitable thickness computation because the insulating gap of the gas is short as epoxy thickness increases.

Keywords