Cables Condition Assessment for Circulating Water Pump & Condenser Extraction Pump

발전소 순환수 및 복수 계통 케이블 건전성 평가

  • Ha, C.W. (Korea Hydro & Nuclear Power Co., Ltd) ;
  • Han, S.H. (Korea Hydro & Nuclear Power Co., Ltd)
  • Published : 2007.07.18

Abstract

There are roughly a hundred types of cables in power plants. The distribution of circuits in a nuclear plant is comprised of 20% instrument cables, 61% control cables, 13% AC power cables, 1% DC power cables, and 5% communication lines. In the nuclear power plant, medium voltage cables are generally included in the scope of systems reviewed for safety and are included in a plant's maintenance program. Medium voltage cables provide power to many critical components in plants, including feed water pumps, circulating water pumps, and condensate pumps. Among these cables, high temperature sections of cables feeding electrical power to the circulating water pump and the condenser extraction pump were found. The evaluation for these cables is performed to find the maximum allowable current and temperature. The result shows that the load current flowed about 85% of the allowable current ampacity, and the temperature of conductor at full load current did not exceed the limited temperature. Therefore, existing cables for circulating water pump and condenser extraction pump system are going to be used during design life.

Keywords