Protection relaying algorithm for DFIG using a DQ equivalent circuit

DQ 등가회로를 이용한 DFIG 보호계전방식

  • Published : 2007.07.18

Abstract

Most of modern wind turbines employs a doubly-fed induction generator (DFIG) system because it has many advantages due to variable-speed operation, relatively high efficiency and it small converter size. The DFIG system uses a wound rotor induction machine so that the magnetizing current of the generator can be fed from both the stator and the rotor. This paper presents a protection relaying algorism for DFIG using the DQ equivalent circuits. The induced voltages calculated from the stator and rotor sides are nearly the same in the steady state. They become different in the DQ equivalent circuits during an internal fault. The proposed algorithm compares the inducted voltages estimated from the stator and the rotor circuit converted into the stationary reference frame. If the difference between the induced voltages exceeds the threshold, the proposed algorithm detects an turn-to-turn fault.

Keywords