Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference (한국전기전자재료학회:학술대회논문집)
- 2006.11a
- /
- Pages.184-185
- /
- 2006
Recovery Characteristics of SFCL According to the Turn's Variation
턴수 변화에 따른 초전도 전류제한기의 회복특성 분석
- Han, Tae-Hee (Chosun Univ.) ;
- Cho, Yong-Sun (Chosun Univ.) ;
- Park, Hyoung-Min (Chosun Univ.) ;
- Nam, Guong-Hyun (Chosun Univ.) ;
- Lee, Na-Young (Chosun Univ.) ;
- Choi, Hyo-Sang (Chosun Univ.) ;
- Lim, Sung-Hun (Soongsil Univ.) ;
- Chung, Dong-Chul (Woosuk Univ.) ;
- Hwang, Jong-Sun (Namdo College) ;
- Choi, Myoung-Ho (Kwangju Health College) ;
- Han, Byoung-Sung (Chonbuk Univ.)
- 한태희 (조선대학교) ;
- 조용선 (조선대학교) ;
- 박형민 (조선대학교) ;
- 남긍헌 (조선대학교) ;
- 이나영 (조선대학교) ;
- 최효상 (조선대학교) ;
- 임성훈 (숭실대학교) ;
- 정동철 (우석대학교) ;
- 황종선 (남도대학) ;
- 최명호 (보건대학) ;
- 한병성 (전북대학교)
- Published : 2006.11.09
Abstract
The flux-lock type superconducting fault current limiter (SFCL) has the attractive characteristics that can adjust the current limiting level by the turns ratio between two coils. Since the recovery characteristics of a superconducting element m the flux-lock type SFCL were dependent on the turns ratio between two coils, the analysis for the recovery characteristics of this type SFCL together with the current limiting characteristic is necessary to apply it to power system. When the applied voltage and load impedance were same, the recovery time of the superconducting element was 0.32sec in case that the turn's ratio between the primary and secondary windings was 63:21. In the meantime, when the turn's ratio of secondary winding increased to 3 times, the recovery time became longer to 0.58sec.