아크지락사고에 대한 사고 판별 및 적응 재폐로 기법

Identification of Arcing Fault and Development of An Adaptive Reclosing Technique about Arcing Ground Fault

  • Kim, H.H. (Dept. of Electrical Eng. Konkuk Univ.) ;
  • Choo, S.H. (Dept. of Electrical Eng. Konkuk Univ.) ;
  • Chae, M.S. (Dept. of Electrical Eng. Kunjang Univ.) ;
  • Park, J.B. (Dept. of Electrical Eng. Konkuk Univ.) ;
  • Shin, J.R. (Dept. of Electrical Eng. Konkuk Univ.)
  • 발행 : 2006.11.03

초록

This paper presents a new one-terminal numerical algorithm for fault location estimation and for faults recognition. The proposed algorithm are derived for the case of most frequent single-phase line to ground fault in the time domain. The arc voltage wave shape is modeled numerically on the basis of a great number of arc voltage records obtained by transient recorder. From the calculated arc voltage amplitude it can make a decision whether the fault is permanent of transient. In this paper the algorithm uses a very short data window and enables fast fault detection and classification for real-time transmission line protection. To test the validity of the proposed algorithm the Electro-Magnetic Transient Program(EMTP/ATP) is used.

키워드