Estimation of Voltage Instability Index Using RLS(Recursive Least Square)

RLS(Recursive Least Square)를 이용한 전압안정도 지수 평가

  • Published : 2006.11.03

Abstract

A Voltage Instability Predictor(VIP) estimates the proximity of a power system to voltage collapse in real time. Voltage Instability Index(Z-index) from VIP algorithm is estimated using LS(Least Square) method. But this method has oscillations and noise of result due to the system's changing conditions. To suppress oscillations, a larger data window needs to be used. In this paper. I propose the new other method which improves that weakness. It uses RLS(Recursive Least Square) to estimate voltage instability index without a large moving data window so this method is suitable for on-line monitor and control in real time. In order to verify effectiveness of the algorithm using RLS method, the method is tested on HydroQuebec system in real time digital simulator(HYPERSIM).

Keywords