An Experimental Study on the Thermal Performance Change of Horizontal-type Geothermal Heat Exchanger with Long-Term Operation

수평형 지열교환기 성능의 경년변화

  • 황광일 (한국해양대학교 기계정보공학부) ;
  • 우상우 (한국해양대학교 대학원 냉동공조공학과) ;
  • 김중헌 (삼성건설 기술연구소) ;
  • 양기영 (삼성건설 기술연구소) ;
  • 신승호 (삼성건설 주택사업본부)
  • Published : 2006.06.21

Abstract

The purpose of this study is on the performance evaluation of horizontally installed GHEX(Geothermal Heat Exchanger, HGHEX) which has been operated for 5 years successfully. Followings are the results. Firstly, in summer season, on Aug. 2000, $33^{\circ}C$ water was flowing out from HGHEX with continuous operating method, and $27{\sim}29^{\circ}C$ with interval operating method on Jul. 2005. But $2.5{\sim}3.0^{\circ}C$ temperature differences are gained from HGHEX. Secondly, in winter season, on Nov. 2000, $25^{\circ}C$ water was flowing out from HGHEX with continuous operating method, and $13{\sim}15^{\circ}C$ with interval operating method on Jan. 2006. But with each operating method, only $0.1^{\circ}C$ and $0.7^{\circ}C$ temperature differences are gained from HGHEX respectively. As the conclusion of this study, at the point of continuos operating method, seasonal balance of heating and cooling loads, and at the point of interval operating method, balance for geothermal restoring time respectively must be considered for better system performances.

Keywords