An Experimental Study on Air-side Performance of Fin-and-Tube Heat Exchangers with Slit Fin

  • Published : 2006.06.21

Abstract

An experimental study is conducted to investigate the effect of the tube row and fin spacing on the air-side heat transfer and friction characteristics of fin-tube heat exchangers with slit fin pattern. A total of twelve samples of fin-tube heat exchangers with the nominal tube diameter of 7 mm, transverse tube pitch of 19 mm and longitudinal tube pitch of 12.5 mm are tested. The thermal fluid measurements are made using a psychometric calorimeter. The raw data are reduced to the desired heat transfer coefficient in terms of j-factor and friction factor of f for various frontal air velocities, fin pitches and number of tube rows.