Uncertainty Analysis of Test Method for Heat Recovery Ventilators

폐열회수 환기유닛의 인증시험 방법에 대한 오차분석

  • Han, H. (School of Mechanical and Automotive Engineering, Kookmin University) ;
  • Choo, Youn-Bok (Graduate School, Kookmin University)
  • Published : 2006.06.21

Abstract

Twenty nine HRV models have been tested for last two years since the attestation system has been started by KARSE. It is the objective of the present study to analyze the performance test results. Uncertainty analysis has been conducted to find the effects of measured variables on the uncertainties of test results. The uncertainty of enthalpy is found to be affected by the uncertainty of wet bulb temperature significantly, but not by that of dry bulb temperature for the present range of parameters. The uncertainty of effective enthalpy efficiency is calculated to be 6%P for the cooling condition, and 3%P for the heating condition approximately. In order to reduce the uncertainty of the test results, the uncertainty of wet bulb temperature should be minimized and the indoor/outdoor test conditions should be modified so as to increase the enthalpy difference.

Keywords