대한설비공학회:학술대회논문집 (Proceedings of the SAREK Conference)
- 대한설비공학회 2006년도 하계학술발표대회 논문집
- /
- Pages.405-410
- /
- 2006
오염발생원의 위치인식에 의한 환기장치 제어방안
Ventilation System Control by Location-Aware of Pollution Source
- Han, H. (School of Mechanical and Automotive Engineering, Kookmin University) ;
- Han, Jung-Il (Graduate School, Kookmin University) ;
- Kwon, Yong-Il (Department of Building Mechnical Engineering, Shinheung College)
- 발행 : 2006.06.21
초록
This paper presents a control algorithm of supply and exhaust diffusers by recognizing a contaminant source location. CFD analysis has been conducted to calculate steady state airflow and concentration distributions in a model room, which has two supply and two exhaust openings on the ceiling. Calculations have been performed for five cases out of nine different ventilation modes by combining on/off control of the supply and exhaust openings. Local mean residual life times are obtained and compared at 9 internal points for each ventilation case. Depending on the contaminant source location, the ventilation system is operated at an optimum ventilation mode, which can results in maximum exhaust performance.
키워드