Proceedings of the SAREK Conference (대한설비공학회:학술대회논문집)
- 2006.06a
- /
- Pages.99-104
- /
- 2006
The Comparative Experiment of Duct Design Method with Equal Friction Loss Method and T-Method on a House Ventilation System
등압법과 T-Method법을 이용한 주택환기시스템 덕트설계법의 비교실험
- Published : 2006.06.21
Abstract
Accurate flow rate distribution has been become a very important part for controling of air change rate since the introduction of house ventilation system. An inappropriate selection of fan due to Incorrect prediction of friction loss makes waste energy. The purpose of this study is to recognize applicability of T-Method at house ventilation system by comparing experiment with T-method, The result of this study is as follows Flow rate is small amount in a house, so duct size must be accurate. And duct design with Equal Friction Loss Method presented large error range. Equal friction loss method is not fit to applicate small amount air flow rate. T-Method predicts accurate flow rate comparatively in a house ventilation system. Error range was 3.5%.
Keywords