Analysis of fault characteristics in Catenary system for protection of AC feeding system

교류 급전시스템 보호를 위한 전차선로 고장특성 분석

  • Published : 2006.07.12

Abstract

This paper analyzes impedance convergence characteristics and harmonics of electric locomotives operation and fault condition. To simulate the various fault and operation condition, AT feeding system and various locomotives are modeled using PSCAD/EMTDC. Analysis shows that impedance are converged into protection area in the case of short fault between catenary and rail or catenary and feeder line but in the case of disconnection fault, impedance is rater bigger so protective relay can't detect the fault. Therefore more analysis of overload and high impedance fault caused disconnection fault is needed.

Keywords