대한전기학회:학술대회논문집 (Proceedings of the KIEE Conference)
- 대한전기학회 2006년도 제37회 하계학술대회 논문집 C
- /
- Pages.1511-1512
- /
- 2006
MV급 케이블 중간접속부의 PD 측정을 위한 UHF-센서와 HFCT-센서의 비교시험
Comparison test for PD measuring about UHF-sensor and HFCT-sensor in cable joint-box of MV grade
- Shin, Dong-Hoon (Wonkwang University) ;
- Lee, Yong-Sung (M-Power Co. LTD) ;
- Kim, Jung-Yoon (M-Power Co. LTD) ;
- Yang, Jong-Seok (Wonkwang University) ;
- Park, Noh-Joon (Wonkwang University) ;
- Park, Dae-Hee (Wonkwang University)
- 발행 : 2006.07.12
초록
In this paper, we measured PD signals from artificial surface defects and corona discharges under laboratory circumstances like the fields using both HFCT-sensor and UHF-sensor for MV grade XLPE cable with AMP, spectrum analyzer and oscilloscope. Also, detected signals were analyzed via PRPDA system in this paper. As a result, in this case of HFCT-sensor, the amount of background noise are larger than as compared to UHF-sensor. There is needed some hardware or software or software algorithm removing background noise effectively for diagnosis the underground power transmission cable in the case of HFCT-sensor.
키워드