IEC 61850 기반 IED의 XML을 이용한 트립로직 구성

The Configuration Method of trip logic for IEC 61850 based IED using XML

  • 발행 : 2006.07.12

초록

As IEC 61850 based substation automation technology is emerging globally, there are many efforts to implement and apply this IEC 61850 standard to substation automation area. IEC 61850 based substation supports ethernet network, standard data model and SCL(substation Configuration Language), etc. These features can provide enough environment to make applied technology which can substitute the legacy relay trip logic configuration method(PLC or Local area reconstruction) to XML based configuration method. This paper suggests new IED trip logic configuration method. The XML based trip logic configuration method can be established using SCL technology And IED trip logic reconfiguration from remote center can be possible under ethernet based technology

키워드