옥상설치 냉각탑에서의 토출공기 재유입량 예측

Prediction of the Individual Reentering Rate of a Cooling Tower within it'S Bank Installed on Building Roof

  • 문선애 (한양대학교 대학원 기계공학과) ;
  • 허진혁 (한양대학교 대학원 기계공학과) ;
  • 최충현 ((주)명진에어테크) ;
  • 이강순 (한양대학교 기계공학부) ;
  • 이재헌 (숭실대학교 기계공학과) ;
  • 유호선 (숭실대학교 기계공학과) ;
  • 이태구 (한양대학교 대학원 기계공학과)
  • 발행 : 2005.11.25

초록

In this paper, the individual reentering rate of the cooling towers installed on a building roof is investigated considering the wind direction and louver wall installation. As the western wind with 5 m/s flows and the louver wall is not installed around the roof. the reentering rate of the cooling towers is predicted about 20%. However the reentering rate is simulated about 5% when the louver wall is installed around the roof. As the southern wind with 5 m/s flows and the louver wall is not installed, the reentering rate of the cooling tower is predicted about 30%.On the contrary, the reentering rate is simulated about 15% when the louver is installed. As a result, if there is no louver wall installed around the roof, the falloff of the cooling capacity would be serious by the reentering of the discharge air. The installation of the louver wall is strongly recommended to prevent the discharge air reentering.