터널 화재로 인한 콘크리트 세그먼트의 손상특성 규명

Fire-induced damage on Shield TBM concrete segment

  • 최순욱 (한국건설기술연구원 지반연구부) ;
  • 장수호 (한국건설기술연구원 지반연구부) ;
  • 이규필 (한국건설기술연구원 지반연구부) ;
  • 배규진 (한국건설기술연구원 지반연구부)
  • 발행 : 2005.03.25

초록

Fire accidents in underground space may bring much loss of lives as well as properties and result in catastrophic disasters. This study aimed to manufacture the high-temperature furnace capable of simulating fire scenarios (RABT and RWS) and carry out the preliminary fire tests to evaluate fire-induced damage in underground structures. Specimens used in the fire tests were the concrete segments generally used in shield TBM tunnels. The simulated fire scenario was set to the RABT curve that is the most representative fire scenario in underground space. From the fire tests, the spalling was estimated to reach approximately 20cm from the surface exposed to fire. In addition, from the observation of core specimens obtained after fire tests, the deteriorated zone of unspalled specimens amounted to approximately 10cm from the surface of spalling.