A Study on Characteristics of Design Parameters for In-line Duct Fan

관류형팬의 설계변수 특성에 관한 연구

  • 박진욱 (제주대학교 대학원, 한국에너지기술연구원) ;
  • 허종철 (제주대학교 기계공학과) ;
  • 이철형 (한국에너지기술연구원) ;
  • 박완순 (한국에너지기술연구원)
  • Published : 2005.12.01

Abstract

The Performance of in-line duct fan depends on the design parameters of impeller and guide vane. such as sweep back angle of impeller, the number of blades, outlet blade angle, guide vane angle etc. In this experimental study total four kinds of impellers having different sweep back angles, $90^{\circ},\;72.5^{\circ},\;55^{\circ},\;37.5^{\circ}$ with 8 guide vanes, different the number of blades, 6ea, 8ea, 10ea, 12ea, different kinds of outlet blade angles, $30^{\circ},\;45^{\circ}.\;60^{\circ}$ and different kinds of guide vane angles, $15^{\circ},\;30^{\circ},\;45^{\circ}$ were selected and their performance measured to investigate the effects of them. The results were non-dimensionalized to compare their performance.

Keywords