Impact and Fatigue Analysis of Superposed Leaf Spring in Electric Power Switch

전력 개폐기의 중첩 판 스프링의 충격 피로 해석

  • Park W.J. (Electro Technology R & D Center, LSIS) ;
  • Ahn K.Y. (Electro Technology R & D Center, LSIS) ;
  • Jeong K.Y. (Mechanical Eng. Dept., Kongju National University)
  • Published : 2005.10.01

Abstract

The automatic load transfer switch (ALTS), a kind of electric power switch, typically automatically transfers electrical loads from a normal electrical power source to an emergency electrical power source upon reduction or loss of normal power source voltage. It can also automatically re-transfer the load to the normal power source when the normal voltage has been restored within acceptable limits. The transfer operation of ALTS is accomplished by a spring-driven linkage mechanism. In order to control or delay the transfer switching time, the ALTS studied in this paper uses the superposed leaf springs, which are subjected to impact leadings in contacting with electrical contacts. Therefore, to confirm whether the springs has enough mechanical endurance in ALTS, we build a finite element model of the superposed lear springs using LS-DYNA and perform the impact and fatigue analysis.

Keywords