Most of electrical fires are caused by short circuits, overheating of wires, deterioration and incomplete connection of wiring devices. The last two cases are predictable before the occurrence of fire because of its slow progress. In this paper, we have simulated the discharge signals caused by the deterioration and incomplete connection of wiring devices using an aged concent to provide information on the characteristics of discharge signals. From the experimental data, we could characterize the frequency spectrums of the discharge signals depending on the cases. The higher frequency components of the signal are attenuated by the capacitance and inductance of power lines as the measuring point is getting away from the discharges. Main frequency components of the discharge signal are existent at 600 kHz - 1.5 MHz in incomplete connections and at 210 kHz - 8 Mhz in deteriorations of the concent.