Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference (한국조명전기설비학회:학술대회논문집)
- 2005.05a
- /
- Pages.254-259
- /
- 2005
A study of the Influence of Forest Fire on Polymer Insulator for UHV
초고압용 폴리머 애자의 산불영향 연구
- Published : 2005.05.13
Abstract
Big fire such as mountain fire my cause the prevention of the functions of the overhead cables and insulators, which may affect the operation of the transmission lines. Therefore, in order to understand the effect of the mountain fire on the polymeric insulator for transmission lines, the author observed the deformation of the sheds of the polymeric insulators and the change of the discs of the porcelain insulators under fire, and investigated the electrical and mechanical characteristics of the insulators after the ignition test. As the result the following conclusions were obtained. First, the porcelain insulator was degraded in electrical characteristics when the insulator was subjected to the fire for approximately 5 minutes; whereas, the polymeric insulator was not degraded though there were some damage on its sheds. Second, after 20 minute exposure to the fire, the polymeric insulator lost a lot of parts of sheds, but the electrical characteristics was lowered by around 20%, but the porcelain insulators were electrically degraded by more than 80%.