미래 배전계통에서의 자동재폐로 동작을 고려한 초전도한류시스템에 관한 연구

A study on SFCL System for Korean future distribution power system application considering auto reclosing actions of protection system

  • 발행 : 2005.11.18

초록

The recovery time of developing SFCL(Superconducting Fault Current Limiter) has an uncertainty. In general, the recovery time is estimated at 1 sec and more, even though the progress of SFCL technology is considered. However, auto reclosing time of circuit breaker is 0.5 sec in Korean distribution power system. It is impossible to apply only one SFCL to power system because the recovery time is over the reclosing time of protection system. This study proposes a new SFCL system for distribution power system application. The proposed systems consider auto reclosing action for the protection in practical power system and consist of tow parallel SFCLs.

키워드