FACTS 기기의 고조파 저감을 위한 이중밴드 히스테리시스 전류 제어에 관한 연구

A Study on Double Band Hysteresis Current Control based on 3-Level Inverter to reduce the harmonic component in output current of FACTS devices

  • 최원경 (고려대학교 전기공학과) ;
  • 최정혜 (고려대학교 전기공학과) ;
  • 김범식 (고려대학교 전기공학과) ;
  • 신은철 (고려대학교 전기공학과) ;
  • 이상빈 (고려대학교 전기공학과) ;
  • 유지윤 (고려대학교 전기공학과)
  • Choi, Won-Kyoung (Korea University Department of Electrical Engineering) ;
  • Choi, Jeong-Hye (Korea University Department of Electrical Engineering) ;
  • Kim, Bum-Sik (Korea University Department of Electrical Engineering) ;
  • Shin, Eun-Chul (Korea University Department of Electrical Engineering) ;
  • Lee, Sang-Bin (Korea University Department of Electrical Engineering) ;
  • Yoo, Ji-Yoon (Korea University Department of Electrical Engineering)
  • 발행 : 2005.04.28

초록

The current control using a conventional hysteresis controller of a STATCOM based on two level VSI (Voltage Source Inverter) has high switching frequency and variable modulation frequency. This will increase the switching loss. In addition, the current error is not strictly limited So, in this paper to reduce the switching frequency and to maintain the constant modulation frequency, a novel double band hysteresis current controller based on 3-level VSI is proposed. A conventional hysteresis current control and a novel hysteresis current control was tested with digital simulation and verified the advantage of the novel hysteresis current controller.

키워드