Proceedings of the KSR Conference (한국철도학회:학술대회논문집)
- 2005.05a
- /
- Pages.867-872
- /
- 2005
A Study on the measurement and Method of Partial Discharge in High Voltage CV Cable
고압 CV 케이블에서의 부분방전 측정과 위치검출 방법에 관한 연구
Abstract
This paper describes the measurement and location method of partial discharges in high voltage CV cables. Coupling capacitors were used to detect partial discharge signal. Impedance characteristic of the coupling circuit and an amplifier with a high Common Mode Rejection Ratio(CMRR) were studied to improve sensitivity of the circuit. From the calibration experiment, the sensitivity of the partial discharge detection circuit was about 100pC. Also, we confirmed that the location of partial discharges in cables can be estimated by calculation of time difference between the first pulse and the second one reflected from the other end of the cable.
Keywords