On-line Condition Monitoring of Thermal Accelerating Aged Transformer by Capacitive Sensor

전기용량 센서를 이용한 가속 열 열화 변압기의 온라인 상태진단

  • Published : 2005.07.18

Abstract

In a transformer, thermal stress is the most influential parameter affecting the aging behavior of insulation system. The aging behavior of insulation system in transformer is determined mainly by the thermal conditions inside the transformer. The thermal stress on the insulation system may occur from operation in a high temperature caused by overloading or local overheating. Thus, this paper investigated the condition monitoring of insulation condition in thermally accelerated aged transformer oils by in-situ sensor. The condition of aged samples was investigated by measurements of relative permittivity i.e. capacitance change by capacitive sensor. Results from the experiments are presented in this paper.

Keywords