Impedance measurement and analysis of overhead medium voltage power lines for broad band power line communication (BPLC)

$1{\sim}30MHz$ 광대역 전력선 통신을 위한 고압 배전선의 임피던스 특성 측정 및 해석

  • Park, Young-Jin (Power telecommunication network group, Korea Electrotechnology Research Institute(KERI)) ;
  • Lee, Jae-Jo (Power telecommunication network group, Korea Electrotechnology Research Institute(KERI)) ;
  • Kim, Kwan-Ho (Power telecommunication network group, Korea Electrotechnology Research Institute(KERI)) ;
  • Lee, Won-Tae (Power telecommunication network group, Korea Electrotechnology Research Institute(KERI))
  • 박영진 (한국전기연구원, 전기정보망 그룹) ;
  • 이재조 (한국전기연구원, 전기정보망 그룹) ;
  • 김관호 (한국전기연구원, 전기정보망 그룹) ;
  • 이원태 (한국전기연구원, 전기정보망 그룹)
  • Published : 2005.07.18

Abstract

In this paper, impedance characteristics of overhead medium-voltage (MV) power lines is reported for power line communication (PLC) over an MV power line network. For analysis, a two-port equivalent network model of MV power lines is derived. By applying the transmission line theory, reflection behavior and impedance of power lines are investigated. For verification, impedance of power lines is measured at a test field for an MV PLC. The results show that impedance of MV power lines is between $200{\Omega}$ and $300{\Omega}$ and converges to a half of their characteristic impedance.