Characteristics of lightning impulse preliminary breakdown discharge under non-uniform electric field in $SF_6/CO_2$ mixtures

불평등전장에서 $SF_6/CO_2$ 혼합기체의 뇌임펄스 전구방전특성

  • 이복희 (인하대학교 차세대 고전압전력기술연구센터) ;
  • 오성균 (인하대학교 차세대 고전압전력기술연구센터) ;
  • 백영환 (인하대학교 차세대 고전압전력기술연구센터) ;
  • 안창환 (인하공업전문대학) ;
  • 전덕규 (서울산업대학교)
  • Published : 2005.07.18

Abstract

This paper presents the experimental results on the preliminary breakdown characteristics under a highly non-uniform electric field in $SF_6/CO_2$ gas mixtures. The impulse preliminary breakdown developments are investigated by the measurements of corona current and light emission images. As a result, the preliminary breakdown development mechanisms for both positive and negative polarities are same. The first streamer corona is initiated at the tip of needle electrode, and the leaders develop with a stepwise propagation and bridge the test gap. The pause time of leader pulses in the positive polarity is significantly shorter than that in the negative polarity. Also, the time interval between the first streamer corona onset and breakdown in the negative polarity was much longer than that in the positive polarity The discharge channel paths in the positive polarity were zigzag. On the other hands, the leader channel in the negative polarity was thicker than that in the positive polarity.

Keywords