Analysis of Furanic Compounds Dissolved in Transformer Oil

변압기에 용존된 Furan계 물질 분석

  • Published : 2005.07.18

Abstract

The electrical and chemical characteristics in transformer insulations are changed due to thermal stress. In the chemical property, as the Kraft paper ages, the cellulose polymer chains breakdown into shorter lengths with a corresponding decrease in both tensile strength and degree of polymerization(DP). Furthermore, cellulous chains breakdown is accompanied by an increase in the content of various furanic compounds within the dielectric liquid. It is known that furanic components in transformer oil come only from the decomposition of insulating paper rather than from the oil itself. Therefore the analysis of furan products provides a complementary technique to dissolved gas analysis for monitoring transformers when we evaluate the aging of insulating paper by the total concentration of carbon monoxide and carbon dioxide dissolved in oil only. In this paper the accelerated aging process of oil--paper samples have been investigated at a temperature up to $140^{\circ}C$ for 500 hours. The oil-paper insulation samples have been measured at intervals of 100 hours. For analysis we used high performance liquid chromatography(HPLC) in accordance with IEC 61198 method.

Keywords